SmartPlate Installation, Operation & Maintenance Manual
CHAPTER 8 – CORRECTIVE MAINTENANCE
Page 78 of 138 AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 OMM-0069_0E
PRI: 11/26/2013 Phone: 800-526-0288 SP-100
WARNING
THE DOUBLE-WALL HEAT EXCHANGER CAN WEIGH UP TO
850 POUNDS, DEPENDING ON THE SMARTPLATE MODEL
SIZE. THEREFORE, USE EXTREME CARE WHEN REMOVING
IT FROM ITS MOUNT. A SUITABLE SLING MUST BE USED TO
LIFT AND REMOVE THE HEAT EXCHANGER FROM ITS
MOUNT.
10. Insert a sling through the four (4) holes in the frame plate and pressure plate, as shown in
Figure 8-19, to safely lift the Heat Exchanger off its mount.
Figure 8-19. Heat Exchanger Lifting Sling
11. To replace the Heat Exchanger with a new assembly, simply reverse the previous steps.
Support the replacement Heat Exchanger using a sling as shown in Figure 8-19 and lower
into position on the Heat Exchanger Mount. Ensure it is properly aligned with the Piping
Assembly and Heat Exchanger Mount. Ensure that the bolts on all four Victaulic
couplings are securely tightened. If the unit is a SPDW61 or SPDW113, re-install the rear
support bracket and verify that adjustable legs are properly positioned.