MC2: 04/23/13 Page 121 of 144
AERCO Control System (ACS)
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
Installation, Operation, and Maintenance Manual
Table G-4: ACS Commands - Continued
No. COMMAND ENTRY RANGE
Outside Air Temperature (°F)
Header Set Temperature (°F)
System Start Temperature (°F)
06 System Start Mode
0 = Temp Only
1 = Temp and Load
0 = Temp Only
Bldg Reference Temperature (°F)
11 Reset Ratio
0.3 to 3.0
(0.1 increments)
1.2
Maximum Header Temperature (°F)
Minimum Header Temperature (°F)
16 Integral Gain (Rep./Min)
0.00 to 9.99
(0.01 increments)
0.15
17 Header Set Mode
1 = Indr/Outdr Reset
0 = Constant Setpt
18 Derivative Gain
-2.00 to 2.00
(0.01 increments)
0.15
21 Aux Relay Close
0 = 100% Fire Rate
1 = 100% and OFF
1 = 100% AND OFF
22 Failsafe Mode
0 = Shutdown
1 = Switch Inputs
0 = Shutdown
23 Fault Relay Mode
1 = No Interlock
2 = Interlock 2
0 = All Faults
24 Alarm Clear Method
0 = Automatic
25 Boiler Operation Mode
1 = Sequential
1 = Sequential